V1.4
96-Zone Expandable Security and Access Control Panel
Reference and Installation Manual
DGP-NE96
www.paradox.ca
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - DGP-NE96

V1.496-Zone Expandable Security and Access Control PanelReference and Installation ManualDGP-NE96www.paradox.ca

Page 2

8 REFERENCE & INSTALLATION MANUALFigure 2-6: Single Zone Input Connections2.14 DOUBLE ZONE CONNECTIONSEnabling the ATZ feature (see section 4.2) a

Page 3 - TABLE OF CONTENTS

DIGIPLEXNE CONTROL PANEL 92.16 COMBUS CONNECTIONSModules can connect anywhere on the 4-wire combus, which can support up to 127 modules. Connect in

Page 4

10 REFERENCE & INSTALLATION MANUALFor TBR-21 compliance, please note the following:1) The DGP-NE96 can be connected to the telephone network via a

Page 5 - INTRODUCTION

DIGIPLEXNE CONTROL PANEL 113 PROGRAMMING METHODSDigiplexNE can be programmed using the following methods:3.1 WINLOAD UPLOADING/DOWNLOADING SOFTWARE

Page 6 - INSTALLATION

12 REFERENCE & INSTALLATION MANUAL4 ZONE PROGRAMMINGAll detection devices connected to the control panel, keypads and zone expansion modules must

Page 7 - DIGIPLEXNE CONTROL PANEL 5

DIGIPLEXNE CONTROL PANEL 134.1.1 Clearing a Zone’s NumberingFor LCD Keypads:1) Enter a section number between [0001] to [0096].2) Press [0] and then

Page 8

14 REFERENCE & INSTALLATION MANUAL4.3.10 24Hr Water Zones*SECTIONS [0101] TO [0196]: FIRST DIGIT = AWhen a 24Hr Water zone opens, whether it is ar

Page 9 - 305m (1000ft)

DIGIPLEXNE CONTROL PANEL 154.5.3 Stay ZonesSECTIONS [0101] TO [0196]: OPTION [3]Only zones with option [3] enabled will be bypassed when the partiti

Page 10 - 2.15 CONNECTING THE DGP2-ZX4

16 REFERENCE & INSTALLATION MANUAL5 KEYSWITCH PROGRAMMINGThe DigiplexNE control panel can support up to 32 keyswitch zones in addition to the 96

Page 11 - Ω EOL resistor. If a line

DIGIPLEXNE CONTROL PANEL 175.2.4 Generates a Utility Key Event on OpenSECTIONS [0601] TO [0632]: FIRST DIGIT = 3When option [3] is enabled, a Utilit

Page 13 - PROGRAMMING METHODS

18 REFERENCE & INSTALLATION MANUAL6 ARMING AND DISARMING OPTIONS6.1 ARMING FOLLOWS PARTITION(Default = disabled) A partition can be set to follow

Page 14 - ZONE PROGRAMMING

DIGIPLEXNE CONTROL PANEL 196.9.1 Auto-Arm TimerWhen Timed Auto-Arming is enabled (see section 6.9), the control panel will attempt to arm the system

Page 15 - 4.3 ZONE DEFINITIONS

20 REFERENCE & INSTALLATION MANUALFigure 6-1: Example of Exit Delay TerminationEnable option [4] in the desired section: 6.16.2 No Exit Delay on R

Page 16 - 4.5 ZONE OPTIONS

DIGIPLEXNE CONTROL PANEL 217 ALARM OPTIONS7.1 BELL/ALARM OUTPUT(Default = only option [1] enabled) When an alarm condition is detected in a partiti

Page 17 - 4.8 KEYPAD NUMBERING

22 REFERENCE & INSTALLATION MANUAL7.5.1 Tamper Bypass OptionsSECTION [3034]: OPTION [7] (Default = enabled) With option [7] enabled in section [30

Page 18 - KEYSWITCH PROGRAMMING

DIGIPLEXNE CONTROL PANEL 238 EVENT REPORTINGFigure 8-1: Event ReportingDialing Enabled/DisabledSection [3036]Option [3]Reporting Account NumbersCen

Page 19 - 5.4 KEYSWITCH OPTIONS

24 REFERENCE & INSTALLATION MANUAL8.1 REPORTING ENABLEDSECTION [3036]: OPTION [3] (Default = disabled) With option [3] ON in section [3036], Event

Page 20 - ARMING AND DISARMING OPTIONS

DIGIPLEXNE CONTROL PANEL 258.2.9 Special Disarming Report CodesWhen using one of the special disarming features listed below, the control panel can

Page 21 - 6.16.1 Exit Delay Termination

26 REFERENCE & INSTALLATION MANUALClose [3916], Late to Close [3917], Early to Open [3926] or Late to Open [3927]. In the desired section enable o

Page 22 - 6.20 MAXIMUM BYPASS ENTRIES

DIGIPLEXNE CONTROL PANEL 271, the control panel will send the Partition 1 Account Number defined in section [3061] followed by the report code.Only

Page 23 - ALARM OPTIONS

DIGIPLEXNE CONTROL PANEL 1TABLE OF CONTENTSINTRODUCTION ... 3Features...

Page 24 - 7.6 KEYPAD PANIC OPTIONS

28 REFERENCE & INSTALLATION MANUAL8.8.1 Maximum Dialing Attempts**SECTION [3056](Default = 008) The number (001 to 255, 000 = 8 attempts) programm

Page 25 - EVENT REPORTING

DIGIPLEXNE CONTROL PANEL 298.16 CLOSING DELINQUENCY TIMER(Default = 000; Disabled) When a partition in the system is disarmed, the control panel wil

Page 26 - 8.2 REPORT CODES

30 REFERENCE & INSTALLATION MANUAL9 DIALER OPTIONS9.1 TELEPHONE LINE MONITORINGSECTION [3036]: OPTIONS [1] AND [2]When enabled, the system verifi

Page 27 - IGIPLEXNE CONTROL PANEL 25

DIGIPLEXNE CONTROL PANEL 3110 PROGRAMMABLE OUTPUTSA PGM is a programmable output that toggles to its opposite state (i.e. a normally open PGM will

Page 28 - 8.5 ACCOUNT NUMBER

32 REFERENCE & INSTALLATION MANUAL11 SYSTEM SETTINGS AND COMMANDS11.1 HARDWARE RESETA Hardware Reset sets sections [0001] to [3991] to default, i

Page 29 - 8.8 EVENT CALL DIRECTION

DIGIPLEXNE CONTROL PANEL 33Delay, Bell Squawk, One-touch Arming, Panic Alarms and many more. All zones, keyswitch zones, user codes and system modul

Page 30

34 REFERENCE & INSTALLATION MANUAL11.17 CLOCK COMPENSATION VALUESECTION [3050](Default = Disabled) When the DigiplexNE’s clock is inaccurate, a cl

Page 31 - DIGIPLEXNE CONTROL PANEL 29

DIGIPLEXNE CONTROL PANEL 35Table 8: Special Characters Catalogue Table 9: Hebrew Keypad Letter AssignmentTable 10: Russian Keypad Letter AssignmentT

Page 32 - DIALER OPTIONS

36 REFERENCE & INSTALLATION MANUAL12 ACCESS CODES12.1 INSTALLER CODE SECTION [1000](Default: 000000) The Installer Code is used to enter the cont

Page 33 - PROGRAMMABLE OUTPUTS

DIGIPLEXNE CONTROL PANEL 3712.6 PARTITION ASSIGNMENTSECTIONS [1002] TO [1999]: ASSIGN AREA SCREEN, OPTIONS [1] TO [8] Each of the 998 User Access Co

Page 34 - SYSTEM SETTINGS AND COMMANDS

2 REFERENCE & INSTALLATION MANUALDaylight Savings Time... 32Battery Charge Current...

Page 35 - DIGIPLEXNE CONTROL PANEL 33

38 REFERENCE & INSTALLATION MANUAL13 ACCESS CONTROL: SYSTEM FEATURESAccess Control defines the days and times people are allowed to enter and exi

Page 36 - S] and [T] keys to

DIGIPLEXNE CONTROL PANEL 39Start Time and End Time during the holidays. An Interval cannot cross into another day (overnight). Schedules are assigne

Page 37 - DIGIPLEXNE CONTROL PANEL 35

40 REFERENCE & INSTALLATION MANUALWhen option [3] is enabled, the Access Card must be presented before the User Access Code is entered.13.13 SKIP

Page 38 - ACCESS CODES

DIGIPLEXNE CONTROL PANEL 4114 WINLOAD SOFTWARE14.1 PANEL IDENTIFIERSECTION [3011](Default = 0000) The Panel Identifier identifies the control panel

Page 39 - 12.7 ACCESS CONTROL

42 REFERENCE & INSTALLATION MANUAL15 USER FEATURES15.1 REGULAR ARMINGThis method is used for the everyday arming of the system. All zones within

Page 40 - ECTIONS [2401] TO [2432]

DIGIPLEXNE CONTROL PANEL 432) Using the scroll keys, highlight Bypass and then press the center action key (Ok).3) Highlight the zone that you wish

Page 41 - DIGIPLEXNE CONTROL PANEL 39

44 REFERENCE & INSTALLATION MANUALStep 3: If more than one Trouble Group appears, highlight the desired group before pressing the center action ke

Page 42

DIGIPLEXNE CONTROL PANEL 4516 APPENDIX 1: PGM PROGRAMMING TABLEEvent Group Event Feature Group Feature Start # End #000 Zone is OK000255 = any Zone

Page 43 - WINLOAD SOFTWARE

46 REFERENCE & INSTALLATION MANUAL012 Special Arming (cont’d)000No Movement Arming 003 003Partial Arming 004 004One-touch Arming 005 005Future Use

Page 44 - USER FEATURES

DIGIPLEXNE CONTROL PANEL 47022 Special Disarming (cont’d)000 (InTouch) Voice Module Disarming 008 008255 Any Special Disarming Event Not Used Not Us

Page 45 - 15.12 TROUBLE DISPLAY

DIGIPLEXNE CONTROL PANEL 31 INTRODUCTIONDigiplexNE is a security and access control system with 8 on-board zone inputs (16 with zone doubling) that

Page 46 - 15.13 TROUBLE LATCH

48 REFERENCE & INSTALLATION MANUAL038 Module Trouble000Combus Fault 000 000Module Tamper 001 001ROM/RAM error 002 002TLM Trouble 003 003Fail to Co

Page 47 - DIGIPLEXNE CONTROL PANEL 45

DIGIPLEXNE CONTROL PANEL 49054 Door Forced Open Restore000255 = any Door NumberDoor Numbers 001 to 032 001 to 032055 Intellizone Triggered000 Zone

Page 48

50 REFERENCE & INSTALLATION MANUALNOTE 1:NOTE 2: This TLM trouble event can only be used with the DigiplexNE control panel models that have two di

Page 49 - DIGIPLEXNE CONTROL PANEL 47

DIGIPLEXNE CONTROL PANEL 51†:** Keyswitch‡ Refer to the Omnia™ Reference and Installation Manual for remote control button programming instructions.

Page 50

52 REFERENCE & INSTALLATION MANUAL17 APPENDIX 2: AUTOMATIC REPORT CODE LISTSystem EventDefault Contact ID Report Codefor sections [4032] to [4037

Page 51 - DIGIPLEXNE CONTROL PANEL 49

DIGIPLEXNE CONTROL PANEL 53AC Failure restore 3 3A1 - AC loss restore AR - AC RestoralBattery Failure restore 3 3A9 - Battery test restore YR - Syst

Page 52

54 REFERENCE & INSTALLATION MANUAL18 APPENDIX 3: CONTACT ID REPORT CODE LISTCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueCID# Report

Page 53 - DIGIPLEXNE CONTROL PANEL 51

DIGIPLEXNE CONTROL PANEL 5519 INDEXSectionsAAC Failure not Displayed ... 34AC Power ...

Page 54

56 REFERENCE & INSTALLATION MANUALCode Follows Schedule ... 37CodesSpecial Alarm Report Codes

Page 55 - IGIPLEXNE CONTROL PANEL 53

DIGIPLEXNE CONTROL PANEL 57Keypad Beep on Successful Arm/Disarm Report ... 30Keypad Lockout ...

Page 56

4 REFERENCE & INSTALLATION MANUAL2 INSTALLATION2.1 RECOMMENDED INSTALLATION PROCEDUREIn order to facilitate installation, we recommend connectin

Page 57 - Sections

58 REFERENCE & INSTALLATION MANUALSSchedule Assignment ... 37Schedule Tolerance Window ...

Page 58

DIGIPLEXNE CONTROL PANEL 5920 WARNINGSFCC WarningsIMPORTANT INFORMATIONThis equipment complies with Part 68 of the FCC rules subpart D and CS-03. I

Page 59 - DIGIPLEXNE CONTROL PANEL 57

60 REFERENCE & INSTALLATION MANUALGrade B Central Station (Level 0)Same as Household Grade A Burglar alarm system unit except:• The ringback featu

Page 61 - UL and ULC Warnings

Printed in Canada - 01/2004 DGPNE96-EI07

Page 62 - Warranty

DIGIPLEXNE CONTROL PANEL 5Figure 2-3: DigiplexNE Control Panel Wiring DiagramWhen installing the combus wires in a noisy environment, or when connecti

Page 63

6 REFERENCE & INSTALLATION MANUAL2.11 CALCULATING POWER REQUIREMENTSSTEP 1: Using Table 1, calculate the total number of power units (PU) required

Page 64

DIGIPLEXNE CONTROL PANEL 7Figure 2-4: Sample Power Requirement Calculations An LCD Keypad (80PU) can be added to the 100ft. or 300ft. wire in Figure