SEKURE Paradox Digiplex DGP-610 Guide d'installation

Naviguer en ligne ou télécharger Guide d'installation pour Systèmes de contrôle d'accès de sécurité SEKURE Paradox Digiplex DGP-610. SEKURE Paradox Digiplex DGP-610 Installation guide Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 64
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
paradox.com
We hope this product performs to your complete satisfaction. Should you have any questions or comments,
please visit paradox.com and send us your comments.
High Security and Access System
EVO48 V1.20
EVO192 V1.20
Installation Guide
Includes Keypad Installation
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - Includes Keypad Installation

paradox.comWe hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit paradox.com and send u

Page 2

6 Reference & Installation ManualFigure 6: Single Zone Input Connections2.14 Double Zone ConnectionsEnabling the ATZ feature (see section 4.3) all

Page 3 - Table of Contents

EVO Control Panel 7Across Separate Buildings: Strip the outer jacket at one end of the shielded cable to expose the shield. In the same building as

Page 4

8 Reference & Installation Manual3 Programming Methods3.1 WinLoad Uploading/Downloading Software*We recommend programming the control panel with

Page 5 - Introduction

EVO Control Panel 94 Zone ProgrammingEnter Section [0400], then enter the number of the zone you want to programEnter the zone’s 8-digit serial and 3

Page 6 - Installation

10 Reference & Installation Manual4.1 Zone ProgrammingTwo different methods can be used to program zones: 4.1.1 Using section [0400]Allows you to

Page 7 - EVO Control Panel 3

EVO Control Panel 114.4.8 24Hr Gas Zones*SECTION [0400]: FIRST DIGIT = 8SECTIONS [0101] TO [0196]: FIRST DIGIT = 8When a 24Hr Gas zone opens, the co

Page 8

12 Reference & Installation Manual4.6.5 Alarm TypesSECTION [0400]: OPTION [2] & [6]SECTIONS [0101] TO [0196]: OPTIONS [5] & [6]4.6.6 Intel

Page 9 - 2.12 Keypad Zone Connections

EVO Control Panel 134.8 EOL on Hardwire ZonesSECTION [3033]: OPTION [7](default = disabled) If detection devices connected to hardwired input termin

Page 10 - 2.15 Combus Connections

14 Reference & Installation Manual5 Remote Control Programming5.1 Hardware Requirements5.2 Remote Control TemplateIt is possible to set up to 16

Page 11 - 2.18 Built-in RTC

EVO Control Panel 156 Keyswitch Programming6.1 Keyswitch NumberingSECTIONS [0501] TO [0532]Keyswitch Numbering allows you to assign any hardwired i

Page 13 - Zone Programming

16 Reference & Installation Manual7 Arming and Disarming Options7.1 Arming Follows Partition(default = disabled) A partition can be set to follow

Page 14 - 4.4 Zone Definitions

EVO Control Panel 17When option [8] is enabled, access is permitted during the programmed holidays (see section 15.8 on page 36). 7.12 Auto-Arming

Page 15 - 4.6 Zone Options

18 Reference & Installation Manual(default = 015) Program the duration of the keypad lockout from 001 to 255 minutes into the desired section. Pro

Page 16 - 4.7 Input Speed

EVO Control Panel 198 Alarm Options8.1 Bell/alarm Output(default = only option [1] enabled) When an alarm condition is detected in a partition, the

Page 17 - 4.9 Keypad Numbering

20 Reference & Installation Manual8.5.1 Tamper Bypass OptionsSECTION [3034]: OPTION [7] (default = enabled) When enabled in section [3034], the co

Page 18 - Remote Control Programming

EVO Control Panel 219 Event ReportingFigure 16: Event ReportingDialing Enabled/DisabledSection [3036]Option [3]Reporting Account NumbersMonitoring

Page 19 - Keyswitch Programming

22 Reference & Installation Manual9.1 Reporting EnabledSECTION [3036]: OPTION [3] (default = disabled) If enabled, the control panel verifies if a

Page 20 - Arming and Disarming Options

EVO Control Panel 239.2.10 Special Alarm Report Codes9.2.11 System Trouble Codes9.2.12 System Trouble Restore CodesIf the Telephone Line Monitoring

Page 21 - 7.18.1 Exit Delay Termination

24 Reference & Installation Manual9.3.2 Arming/Disarming Schedule Tolerance Window(default = 000) The Arming/Disarming Schedule Tolerance Window l

Page 22 - 7.22 Maximum Bypass Entries

EVO Control Panel 25sequentially, skipping any disabled numbers and stopping once all selected telephone numbers have been reached. If the control p

Page 23 - Alarm Options

EVO Control PanelTable of ContentsIntroduction... 1Features of EVO48 ...

Page 24 - 8.6 Keypad Panic Options

26 Reference & Installation Manualenabled, the control panel sends the Zone Alarm Restore report codes (see section 9.2) to the monitoring station

Page 25 - Event Reporting

EVO Control Panel 2710 Dialer Options10.1 Telephone Line MonitoringSECTION [3036]: OPTIONS [1] AND [2]When enabled, the system verifies the existen

Page 26 - 9.2 Report Codes

28 Reference & Installation Manual11 VDMP3 Voice Module11.1 VDMP3 Installation Instructions11.2 Feature activation (PGMs)Using the VDMP3, it is p

Page 27 - 9.2.11 System Trouble Codes

EVO Control Panel 2912 Programmable OutputsThe control panel provides a maximum of 100 mA to PGM1 to PGM4. PGM5 is a 5A/28Vdc N.O./ N.C. relay out

Page 28 - 9.8 Event Call Direction

30 Reference & Installation Manual13 System Settings and Commands13.1 Hardware ResetA Hardware Reset sets sections [0001] to [3991] to default. O

Page 29 - EVO Control Panel 25

EVO Control Panel 3113.10 PartitioningSECTION [3031]: OPTIONS [1] TO [8](default = partition 1 enabled) The control panel can provide up to eight co

Page 30

32 Reference & Installation Manual13.22 Auto Trouble ShutdownSECTION [3021](default = 00) If a trouble occurs more than the number programmed, the

Page 31 - Dialer Options

EVO Control Panel 33Table 11: Russian Keypad Letter AssignmentTable 13: Hebrew Special Characters CatalogueTable 14: Russian Special Characters Cata

Page 32 - VDMP3 Voice Module

34 Reference & Installation Manual14 Access Codes14.1 Installer Code SECTION [1000](default = 000000) The Installer Code is six digits in length

Page 33 - Programmable Outputs

EVO Control Panel 3514.6 Partition AssignmentSECTIONS [1002] TO [1999]: ASSIGN AREA SCREEN, OPTIONS [1] TO [8] Each of the 998 user access codes can

Page 34 - System Settings and Commands

Reference & Installation ManualProgrammable Outputs... 29PGM Activation Event...

Page 35 - S] and [T] keys to scroll

36 Reference & Installation Manual15 Access Control: System FeaturesFor details on connecting Access Control devices, refer to the “Digiplex Acce

Page 36 - 13.25 System Labels

EVO Control Panel 37Figure 20: Example of a Schedule Tolerance WindowThe Schedule Tolerance Window applies to Access Schedules only (see section 15.

Page 37 - EVO Control Panel 33

38 Reference & Installation Manual16 WinLoad Software16.1 Panel IdentifierSECTION [3011](default = 0000) Program the same Panel Identifier in the

Page 38 - Remote Control Assignment*

EVO Control Panel 39Figure 21: Upgrading Control Panels and ModulesFigure 22: Upgrading EVO641-EVO641R KeypadsTo computer’s 9-pin serial port (DB-9)

Page 39 - 14.7 Access Control

40 Reference & Installation Manual17 Appendix 1: Automatic Report Code ListSystem EventDefault Contact ID Report Codewhen using sections [4032] t

Page 40

EVO Control Panel 41Zone tamper restore (##) 3 144 - Sensor tamper restore TR - Tamper RestoralKeypad Lockout 1 421 - Access denied JA - User Code T

Page 41 - EVO Control Panel 37

42 Reference & Installation Manual18 Appendix 2: Contact ID Report Code ListCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueCID# Report

Page 42 - WinLoad Software

EVO Control Panel 43455 Auto-Arm Failed 9E COMMUNICATION DISABLES - 550 & 560 609 Video Xmitter Active C5456 Partial Arm 9F 551 Dialer Disabled

Page 43 - CONV4USB

44 Reference & Installation Manual19 Appendix 3: Keypad Installation Instructions1.1 Keypad Installation Instructions1.1.1 Connecting the Keypads

Page 44

EVO Control Panel 453.1 Programming3.1.1 Entering Module Programming ModeThe keypad is programmed through the control panel. To do so, you must firs

Page 45

EVO Control Panel 11 IntroductionThe Digiplex EVO is a security and access control system with 8 on-board zone inputs (16 with zone doubling) that

Page 46

46 Reference & Installation Manual3.3.12 Keypad Tamper EnableSECTION [006]: OPTION [5]3.3.13 Combus Voltmeter1. From Normal Mode press and hold th

Page 47 - EVO Control Panel 43

EVO Control Panel 473.5.11 Beep on TroubleSECTION [005]: OPTIONS [1] TO [4]Option [1] OFF=Beep disabled: System Troubles and Clock LossOption [1] ON

Page 48 - ECTION [520]

48 Reference & Installation Manual3.6.13 Beep Timer For Door Left Open AlarmSECTION [012]Enter any value between 001 and 255 to determine the numb

Page 49 - 3.3 EVO641 Programming

EVO Control Panel 494.1.5 Exit Confidential ModeSection [009] Option [2]Option [2] ON = Exit Confidential Mode by entering an access code.Option [2]

Page 50 - 3.5 EVO641R Programming

50 Reference & Installation Manual5 IndexAAC Failure not Displayed ... 32AC Power ...

Page 51 - 3.6 Access Control Options

EVO Control Panel 51Delay Alarm Transmission ... 12Delay Alarm Transmission Timer ...

Page 52 - 4.1 DGP2-648BL Programming

52 Reference & Installation ManualNNo AC Fail Display ... 32No Bell Cut-Off on Fire Alar

Page 53 - EVENT GROUP, FEATURE GROUP

EVO Control Panel 53Test reports ... 25Timed and Hourly Test Transmission ...

Page 54 - 5 Index

6 WarningsFCC WarningsIMPORTANT INFORMATIONThis equipment complies with Part 68 of the FCC rules subpart D and CS-03. Inside the cover of this equipm

Page 55 - EVO Control Panel 51

Household Fire Warning Systems (US and Canada)• At least one model EVO641 keypad shall be used with the system.• One Paradox model MR3-UL end-of-line

Page 56

2 Reference & Installation Manual2 Installation2.1 Recommended Installation Procedure1. Connect a small group of modules, including a keypad. See

Page 57 - EVO Control Panel 53

CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electrical inspection authority, or electric

Page 61

Printed in Canada - 10/2007 paradox.com EVO-EI03

Page 62

EVO Control Panel 3Figure 3: EVO Control Panel Wiring DiagramAUX Power (Auxiliary):Provides up to 700mA. Refer to Table 1 on page 4 When installing th

Page 63

4 Reference & Installation Manual2.11 Calculating Power Requirements1. Using Table 1, calculate the total number of milliamps (mA) required by eac

Page 64

EVO Control Panel 5Figure 4: Sample Power Requirement Calculations Do not use the same transformer for the control panel and the external power supp