ARDWARE
R
ESET
A Hardware Reset sets sections [0001] to [3991] to default, including the
Installer and System Master Codes. Only the Panel ID, PC Password, PC
Telephone Number and Event Buffer are not reset. A Hardware Reset
cannot be performed on a control panel with the Installer Code Lock
enabled (see section 12.3).
1) Make sure the Installer Code Lock is disabled
2) Remove the battery and AC power from the control panel.
3) Place the
RESET
jumper on the reset pins of the control panel.
4) Re-connect the AC power and the battery to the control panel.
5) Wait 10 seconds and remove the jumper.
12.2 S
OFTWARE
R
ESET
Performing a software reset will set certain parameters to default values or
program certain sections with a set of pre-defined values. To do so:
1) Place the
RESET
jumper on the reset pins of the control panel.
2) Enter Panel Programming Mode (see section 4.4).
3) Enter the 4-digit [
SECTION
] of the software reset you wish to perform:
Do not remove power from the control panel.
12.3 I
NSTALLER
C
ODE
L
OCK
(Default = 000) Enter 147 into section [3001] to lock all programming.
When 147 is programmed, performing a hardware reset as described in
section 12.1 will not affect the current panel settings. To remove the
Installer Lock, enter 000 into section [3001].
12.4 D
AYLIGHT
S
AVINGS
T
IME
(Default = enabled) When option [3] is enabled, the control panel adjusts
the system's clock (time) for daylight saving changes. At 2:00AM on the first
Sunday of a full weekend in April, the control panel will add one hour to the
programmed time (clock). At 2:00AM on the last Sunday of a full weekend
in October, the control panel will subtract one hour from the time (clock).
12.5 B
ATTERY
C
HARGE
C
URRENT
When option [5] is enabled, the batterys charge current is 700mA (min.
40VA transformer). When option [5] is disabled, the charge current is
350mA. Depending on the batterys capacity, enable or disable the option:
12.6 S
ERIAL
P
ORT
B
AUD
R
ATE
When option [8] is enabled, the serial ports baud rate is 38,400 baud.
When option [8] is disabled, the baud rate is 19,200 baud. Depending on
the baud rate set in WinLoad or NEware, enable or disable option [8]:
If communication between the control panel and the computer is
experiencing difficulty at 38,400 baud, especially over long
distances, disable option [8] and reduce the baud rate of the
software to 19,200 baud.
12.7 P
ARTITIONING
(Default = only partition 1 enabled) The control panel can provide up to
eight completely independent partitions. Most features and options can be
independently set for each partition such as Event Reporting, Entry/Exit
Delay, Bell Squawk, One-touch Arming, Panic Alarms and many more. All
zones, keyswitch zones, user codes and system modules are assigned to
specific partitions, making this a true partitioned system. Enable the
option(s) that correspond to the desired partition(s):
12.7.1 Panel Partition Assignment
(Default = 00) The control panel will report system events as originating
from one or all enabled partitions. The System Troubles (i.e. AC Failure,
TLM Failure, etc.) can only be viewed through the partitions enabled in this
section. Enter one of the following values:.
Section Description
[4040]
Entering this section resets the programmable sections from
[0001] to [3991] to default (even if Installer Code Lock is
enabled). The Event Buffer, Panel ID, PC Password, PC
Telephone Number and Zone, Door, Partition and User Labels
(see section 13.4) will not reset.
[4041] Entering this section resets the System Master Code to 123456.
[4042]
Entering this section resets all Zone Programming sections from
[0001] to [0196], [0201] to [0296] and [0961] to [0984] to default.
[4043]
Entering this section resets the Access Control sections, except
Door Labels (see section 12.22), from [2201] to [2712] to default.
[4044]
Entering this section resets all User Access Code Programming
sections from [1001] to [1999] and [2001] to [2199] to default.
User Labels (see section 13.4) will not be reset.
[4045]
Entering this section resets all control panel settings from [3020]
to [3043] and from [3900] to [3991] and all the Dialer sections
from [3051] to [3081] to default.
[4046]
Entering this section resets all Partition Settings, except Partition
Labels (see section 12.22), from [3101] to [3829] to default.
[4047]
Entering this section resets Keyswitch Programming sections
from [0501] to [0832] and all Programmable Outputs sections
from [0901] to [0939] to default.
[4048]
Entering this section resets the User Labels from the User
Access Codes, the Zone Labels from [0301] to [0396], Door
Labels from [2301] to [2332], Partition Labels [3100], [3200],
[3300], [3400], [3500], [3600], [3700] and [3800] to default.
Option Feature
[5]
ON
700mA
[5]
OFF
350mA (default)
Option Feature
[8]
ON
38,400 baud
[8]
OFF
19,200 baud (default)
Option Description Option Description
[1] Partition 1 [5] Partition 5
[2] Partition 2 [6] Partition 6
[3] Partition 3 [7] Partition 7
[4] Partition 4 [8] Partition 8
Value Description Value Description
00 All enabled partitions
01 Control Panel in Partition 1 05 Control Panel in Partition 5
02 Control Panel in Partition 2 06 Control Panel in Partition 6
03 Control Panel in Partition 3 07 Control Panel in Partition 7
04 Control Panel in Partition 4 08 Control Panel in Partition 8